Kv to Cv Converter and Flow Calculator
Convert between the metric flow coefficient Kv and the US flow coefficient Cv — or find the liquid flow through a valve from its Kv or Cv and the pressure drop across it. You can also work backwards: enter a flow and a pressure drop to get the Kv or Cv a valve must have.
Formula
| Symbol | Meaning | Unit |
|---|---|---|
| Kv | Metric flow coefficient | m³/h at 1 bar drop |
| Cv | US flow coefficient | US gpm at 1 psi drop |
| Q | Volumetric flow rate | m³/h or US gpm |
| Δp | Pressure drop across the valve | bar or psi |
| SG | Specific gravity of the liquid (1.0 for water) | — |
The two coefficients describe the same valve in different unit systems: Kv is the flow of water in m³/h through the valve at a pressure drop of 1 bar, and Cv is the flow of water in US gallons per minute at a pressure drop of 1 psi. Flow grows with the square root of the pressure drop, so doubling the flow needs four times the pressure drop — and a heavier liquid (higher SG) flows less at the same drop.
Worked examples
Example 1 — Convert Kv to Cv
A valve rated Kv 10 is rated Cv 11.56.
Example 2 — Convert Cv to Kv
A valve rated Cv 50 is rated Kv 43.25.
Example 3 — SI: flow from Kv and pressure drop
- , , water ()
Example 4 — US: flow from Cv and pressure drop
- , , water ()
Example 5 — Required Kv from flow and pressure drop
- , , water ()
The valve must have a rated Kv of at least 10 at full opening.
Assumptions and limits
- Liquids only. These relations are for incompressible liquids. They do not apply to gases or steam, where density changes across the valve.
- Turbulent, non-choked flow. The square-root relation assumes fully turbulent flow without flashing or cavitation. If the pressure drop is large enough for the liquid to flash or cavitate, the flow stops following this formula and the valve can be damaged — check choked-flow conditions per IEC 60534.
- Rated Kv/Cv is at full opening. A valve’s published Kv or Cv is measured fully open. At part opening the effective coefficient is lower, so size on the required Kv at the normal operating point, not on a throttled position.
- Specific gravity is relative to water. SG is the liquid density divided by the density of water. Enter 1.0 for water and the correct SG for anything else — a heavier liquid needs a larger valve for the same flow.
- The conversion factor is a rounded constant. This site uses Cv = 1.156 · Kv and Kv = 0.865 · Cv. Some sources quote 1.165 / 0.857; see the FAQ for why the difference is small.
Next step
The valve pressure drop is part of the system loss. Add it to elevation and friction to get the pump's total dynamic head: Total dynamic head (TDH) calculator
FAQ
What do Kv and Cv actually mean?
Kv is the flow of water, in m³/h, that passes through a fully open valve at a pressure drop of exactly 1 bar. Cv is the same idea in US units: the flow of water, in US gallons per minute, at a pressure drop of exactly 1 psi. Both are measured at full opening, so a larger Kv or Cv means a larger (or more open) valve, not a different valve type.
Some sources say Cv = 1.165 · Kv (or Kv = 0.857 · Cv). Which is right?
Both are roundings of the same unit conversion — the 1.156 factor follows from the definitions of the two coefficients (m³/h at 1 bar versus US gpm at 1 psi), while 1.165 comes from rounding at a different reference temperature for water. This site uses 0.865 / 1.156. The two versions differ by under 1%, which is smaller than the usual spread between catalogue values, so use one factor consistently and do not mix them.
Can I use this calculator for gas or steam?
No. The formulas assume an incompressible liquid with constant density. For a gas or steam the density changes across the valve, so the square-root relation does not apply and you need the gas sizing equations in IEC 60534 instead.
What is flashing and cavitation, and why do they matter here?
If the pressure inside the valve falls to the liquid vapour pressure, bubbles form (flashing) and may collapse downstream (cavitation). Once that happens the flow no longer rises with the square root of the pressure drop — the flow is choked — and the collapsing bubbles can erode the valve trim. This calculator assumes neither happens; for a large pressure drop, check the choked-flow condition per IEC 60534.
What specific gravity should I enter?
Enter 1.0 for water. For any other liquid, SG is its density divided by the density of water — for example a liquid with a density of 850 kg/m³ has SG 0.85. A heavier liquid (SG above 1) flows less than water at the same pressure drop, so it needs a larger Kv for the same flow.
Sources
- CaptiveAire Toolbox — Cv / Kv conversion and flow equations
- Electrical Volt — Kv to Cv conversion
- Instrumentation Tools — derivation of the 1.156 factor from the unit definitions of Kv and Cv
- IEC 60534 — Industrial-process control valves (flow capacity and sizing)
For preliminary estimates only. Verify against manufacturer data and the governing standard before purchase or installation.